Rack Floor Rack Row Rack Row Pos STAR Day 1 Sub-System Rack Name Item Name Total in Rack (or Unit) AC supply Average current/ AC Plug Peak current/ AC Plug Breaker Size (per plug or strip) Total# of Branch Lines / spread sheet line Total Power KVA Comments
                            revised (8/6/98)
DAQ House                            
                             
D A 1 no DAQ Integr. Reserve (future) 9U VME Crates 2 208 9   20 3   Use 1500 watt /crate
            spare 3 120 2   20 1    
                             
D A 2 no DAQ Integr. Reserve (future) 9U VME Crates 3 208 9   20 3   Use 1500 watt /crate
            spare 3 120 2   20 1    
            rack front 2 120 2         in front of rack
                             
D A 3 yes DAQ DAQ- SVT 9U VME Crates 3 208 10   20 3   VME - 5V@250A, 3.3V@60A - 1720 watt
            spare 3 120 2   20 1    
                             
D A 4 yes DAQ DAQ- SVT 9U VME Crates 3 208 10   20 3   VME - 5V@250A, 3.3V@60A - 1720 watt
            spare 3 120 2   20 1    
            rack front and back 4 120 1         in front and back of rack
                             
D A 5 yes DAQ DAQ-TPC 9U VME Crates 3 208 10   20 3   VME - 5V@250A, 3.3V@60A - 1720 watt
            spare 3 120 2   20 1    
                             
D A 6 yes DAQ DAQ-TPC 9U VME Crates 3 208 10   20 3   VME - 5V@250A, 3.3V@60A - 1720 watt
            spare 3 120 2   20 1    
            rack front 2 120 2         in front of rack
                             
D A 7 yes DAQ DAQ-TPC 9U VME Crates 2 208 10   20 2   VME - 5V@250A, 3.3V@60A - 1720 watt
            6U VME Crates 1 120 10   20 1   For trigger
            spare 3 120 2          
                             
D A 8 yes DAQ DAQ-Tape 6U VME Crate 2 120 10   20 2   1000 watt/crate
            spare 8 120 1   20 1   1000 watt for taping
            rack front and back 4 120 1         in front and back of rack
                             
D A 9 yes DAQ DAQ-TPC 9U VME Crates 3 208 10   20 3   VME - 5V@250A, 3.3V@60A - 1720 watt
            spare 3 120 2   20 1    
                             
D A 10 yes DAQ DAQ-TPC 9U VME Crates 3 208 10   20 3   VME - 5V@250A, 3.3V@60A - 1720 watt
            spare 3 120 2   20 1    
            rack front 2 120 2         in front of rack
                             
D A 11 yes DAQ DAQ-TPC 9U VME Crates 3 208 10   20 3   VME - 5V@250A, 3.3V@60A - 1720 watt
            spare 3 120 2   20 1    
                             
D A 12 no DAQ DAQ-FTPC 9U VME Crates 3 208 10   20 3   VME - 5V@250A, 3.3V@60A - 1720 watt
            spare 3 120 2   20 1    
            rack front and back 4 120 1         in front and back of rack
                             
D A 13 no DAQ DAQ-FTPC 9U VME Crates 3 208 10   20 3   VME - 5V@250A, 3.3V@60A - 1720 watt
            spare 3 120 2   20 1    
                             
D A 14 no DAQ Integr. Reserve 9U VME Crates 3 208 10   20 3   VME - 5V@250A, 3.3V@60A - 1720 watt
            spare 3 120 2   20 1    
            rack front 2 120 2         in front of rack
                             
D A 15 no DAQ Integr. Reserve (future) 9U VME Crates 3 208 10   20 3   VME - 5V@250A, 3.3V@60A - 1720 watt
            spare 3 120 2   20 1    
                             
D A 16 no DAQ Integr. Reserve (future) 9U VME Crates 3 208 10   20 3   VME - 5V@250A, 3.3V@60A - 1720 watt
            spare 3 120 2   20 1    
            spare 3 120 2   20 1    
            rack front 2 120 2         in front of rack
                             
D C 1 yes RHIC Communication misc items 8 120 1   20 1   RHIC Rack. STAR does not need to supply power
            rack front conven. 2 120 2          
                             
D C 2 yes Slow Controls Slow Controls 6U VME Crate 1 120 10   20 1   1000 watt/crate
            Ethernet 1 120 3   20 1   Use 500 watt for this breaker
              6 120 1         one plug strip will do
                             
                             
D C 3 yes Integration Integr. Reserve 9U VME Crates 1 208 6   20 1   Spare Crate
            spare 3 120 2   20 1    
            rack front and back 4 120 1         in front of rack
                             
D C 4 yes Integration Integr. Reserve spare 3 120 2   20 1    
                             
D C 5 yes Integration Integr. Reserve 9U VME Crates 1 208 6   20 1   Spare Crate
            spare 3 120 2   20 1    
            rack front 4 120 1         in front of rack
                             
      yes on-line not done yet                  
        computing                    
                             
Clean Power - WAH or Assembly Hall                            
                             
1 A 1 yes Trig/CTB/TOF Trig 9U VME Crates 3 208 9   20 3   1500 watts/VME Crate
            spare 5 120 3   20 1    
                             
1 A 2 yes Trig/CTB/TOF Trig L1 TCD 9U VME Crates 3 208 9   20 3   5V@200A VME
            spare 3 120 2   20 1    
            rack front conven. 2 120 1   20 1   in front of rack
                             
1 A 3 yes Trig/CTB/TOF Trig L0 DSM 9U VME Crates 3 208 9   20 3   5V@200A VME
            spare 5 120 2   20 1    
                             
1 A 4 yes Trig/CTB/TOF Trig VPD/VTX 9U VME-VPD electronics 2 208 9   20 2   5V@200A VME
            HV Power supply 1 208 9   20 1   LeCroy 1440 - 1500 watt
            fans 2 120 1   20 1    
            spare 3 120 2          
            rack front and back conven. 4 120 1         in front of rack
                             
1 A 5 yes Trig/CTB/TOF Trig MWC 9U VME Crate 3 208 9   20 3    
            spare 5 120 2   20 1    
                             
1 A 6 yes Trig/CTB/TOF CTB/TOF VME 9U VME Crate 2 208 9   20 2    
            spare 5 120 2   20 1    
            rack front conven. 2 120 1         in front of rack
                             
1 A 7 yes Trig/EMC EMC Trigger 9U VME Crate 3 208 9   20 3    
            spare 5 120 2   20 1    
                             
1 A 8 no EMC Trig EMC 9U VME crates for EMC 3 208 9   20 2   Revised from EMC
            6U VME 1 120 6   15 1    
            spare 3 120 3   20 1    
            rack front and back conven. 4 120 1         in front of rack
                             
1 A 10 yes TPC TPC-Laser Control VME Crate - optics cntr. 1 120 5   20 1   480 watt - use Howard Wieman (HW) document
            VME Crate - laser trig 1 120 3         280 watt
            plug strip 6 120 2   20 1   Assume 1000 watts of power
            rack front conven. 2 120 1         in front of rack
                             
1 B 1 yes Trig/CTB/TOF CTB/TOF LV Low Voltage for Trays 1 208 21   30 1   3500 watt - Ed Platner
            Low Voltage for MWC 1 208 21   30 1   3500 watt - Ed Platner
            fans 2 120 1   20 1    
            spare 3 120 2          
            rack front conven. 2 120 2         in front of rack
                             
1 B 2 yes Trig/CTB/TOF CTB/TOF LV Low Voltage for TOF 2 208 21   30 2   3500 watt - Ed Platner
            fans 2 120 1   20 1    
            spare 3 120 3          
                             
1 B 3 yes Trig/CTB/TOF CTB/TOF LV Low Voltage for TOF 2 208 21   30 2   3500 watt - Ed Platner
            fans 2 120 1   20 1    
            spare 3 120 2          