Press

Indication

What Key Does

S

PAS

Start up and display password

0

ENTER

PAS

Confirm Password

0

ENTER

d P

Display decimal point

1111

ENTER

loE

Minimum input

0.000

ENTER

hiE

Maximum input

1.000

ENTER

lo

Lowest displayed value

0

ENTER

Hi

Highest displayed value

1500

ENTER

SP

Set point for alarm #1

40

ENTER

uP

Alarm level #1 (must be "uP")

ENTER

HYS

Hysteresis for alarm level #1

0.0

ENTER

DEL

Time delay before alarm #1 trips

2

ENTER

nE

Relay status for alarm #1

ENTER

SP

Set point for alarm #2

40

ENTER

uP

Alarm level #2 (must be up)

ENTER

HYS

Hysteresis for alarm level #2

0.0

ENTER

DEL

Time delay before alarm #2

2

ENTER

nE

Relay status for alarm #2

'S'

run

Exit Program Mode

This sequence checks to see if the proper values are programmed into the Ground Integrity Detector.

November 16, 1998